30167
Georgin
RDN 211 002 Isolation Amplifier 2
24/48VDC channels
2 inputs (contact or NAMUR). 1
SPDT relay output per channel
Supply voltage 24/48 VDC
ATEX classification CE 0081 Ex II (1) G/D
SIL 2 classification according to IEC 61508
Connection via pluggable spring terminals
Customs tariff number: 8504 3180
Country of origin: France / EU
Ref. RDN211002
Intrinsic safe relay
Input: 2 x switch or proximity sensor
Output: 2 x relays (1 RT) per channel
Option: without, clamp terminals
Power supply: 24/48 Vdc
Rail DIN mounting interface
ATEX information:
EC type examination certificate LCIE 02
ATEX 6104X
[Ex ia] IIC (-20 °C < Ta < 60 °C)
Group II (surface) - category (1) G/D
Installation in a safe zone
barrier for equipment installed in zone
0,1,2 gas
or zone 20, 21, 22 dust
See leaflet for safe use