Janitza - Umg 96-Pa, 24-90v 5232002
Energy meter UMG 96-PA
with clock, battery and data memory (4MB)
Front Panel Mount Device, 96 x 96 x 86 mm (WxHxD)
Supply voltage:
AC 24 V - 90 V (50/60 Hz) or
DC 24 V - 90 V,
Installation category: 150 V CAT III
Measurement in TN and TT networks
Measurement of harmonics up to the 25th
3 voltage measurement inputs:
Measurement category: 600 V CAT III
Measurement in 3-phase 4-conductor systems up to 417
V / 720 V (+ -10%) according to IEC
Measurement in 1-phase 2-conductor systems up to 480
V (+ -10%)
3 current measuring inputs:
Measurement category: 300V CAT II
Rated current 5A / 1A adjustable
Current measuring range: 5 mA ... 6 A
Resolution: 0.1mA
peripherals:
3x digital inputs and outputs each
1x analog output
1x RS485 (Modbus RTU)
Accessories (included):
33.03.360 Installation instructions incl.
Safety instructions and "Software GridVis"
Getting started
52.22.251 Mounting kit
52.00.008 RS485 terminator 120
ohm
Programming software "GridVis Basic" downl