"Kromschröder" markasına ait modeller;
88601642
 On-site housing for control and ignition
 and monitoring of modulating
 fan-assisted burners. For
 Continuous operation with ionization monitoring
 or UV monitoring with UV probe UVD.
 Intermittent operation with UV probe
 UVS. Display of the program status, the
 Device parameters and the flame signal.
 Manual operating mode. Diagnostics and
 Setting device parameters via
 optical interface and PC software
 BCSoft. EU-certified. AGA approved.
 Market: European market, EU-certified
 Mains voltage: 230 V~, 50/60 Hz
 Electronic ignition: Single-pole
 Blower control: Relay 3 A
 Flap control: Three-point step
 Flame monitoring: Ionic
 (Continuous/intermittent operation) or UV
 (intermittent with UVS)
 Digital input function: Monitoring
 DGmax.
 Electrical connection: With base
 11 Minimum burner pause time tBP: 0 s
 07 Burner start-up attempts: 1
 22 Switch-on delay time tE: 0 s
 21 Pre-ignition time tVZ: 3 s
 12 Safety time 1 Start-up burner/ignition
 tSA1: 3 s
 13 Flame stabilization time 1 bru./ignition bru.
 tFS1: 2 s
 14 Safety time 2 Start-up main burner
 tSA2: 5 s
 15 Flame stabilization time 2
 Main burner tFS2: 2 s
 29 Delay time rule release tRF: 0 s
 10 Minimum operating time tB: 0 s
 09 Safety time during operation tSB: 1 s
 27 V2 in burner operation: One
 08 Behavior after flame failure in the
 Operation: Fault shutdown
 02 Burner shutdown threshold: 1 micro A
 17 UVS check (1 x in 24 h): Off
 16 Operating time in manual mode: up to 5
 Limited minutes: No
 30. Custom password: ----
 04 Air monitoring during pre-rinse: One
 05 Air monitoring in the workplace: One
 23 Gas pressure monitoring min.: Off
 24 Function Digital Input: Monitoring
 DGmax.
 20 Blower pre-run time tGV: 3 s
 25 Flap control: One
 06 Pre-rinse on every start: One
 18 Pre-rinse time tPV: 10 s
 19 Rinse time tPN: 0 s
BCU370WI1FEU0D1

Kromschröder
88601642 On-site housing for control and ignition and monitoring of modulating fan-assisted burners. For Continuous operation with ionization monitoring or UV monitoring with UV probe UVD. Intermittent operation with UV probe UVS. Display of the program status, the Device parameters and the flame signal. Manual operating mode. Diagnostics and Setting device parameters via optical interface and PC software BCSoft. EU-certified. AGA approved. Market: European market, EU-certified Mains voltage: 230 V~, 50/60 Hz Electronic ignition: Single-pole Blower control: Relay 3 A Flap control: Three-point step Flame monitoring: Ionic (Continuous/intermittent operation) or UV (intermittent with UVS) Digital input function: Monitoring DGmax. Electrical connection: With base 11 Minimum burner pause time tBP: 0 s 07 Burner start-up attempts: 1 22 Switch-on delay time tE: 0 s 21 Pre-ignition time tVZ: 3 s 12 Safety time 1 Start-up burner/ignition tSA1: 3 s 13 Flame stabilization time 1 bru./ignition bru. tFS1: 2 s 14 Safety time 2 Start-up main burner tSA2: 5 s 15 Flame stabilization time 2 Main burner tFS2: 2 s 29 Delay time rule release tRF: 0 s 10 Minimum operating time tB: 0 s 09 Safety time during operation tSB: 1 s 27 V2 in burner operation: One 08 Behavior after flame failure in the Operation: Fault shutdown 02 Burner shutdown threshold: 1 micro A 17 UVS check (1 x in 24 h): Off 16 Operating time in manual mode: up to 5 Limited minutes: No 30. Custom password: ---- 04 Air monitoring during pre-rinse: One 05 Air monitoring in the workplace: One 23 Gas pressure monitoring min.: Off 24 Function Digital Input: Monitoring DGmax. 20 Blower pre-run time tGV: 3 s 25 Flap control: One 06 Pre-rinse on every start: One 18 Pre-rinse time tPV: 10 s 19 Rinse time tPN: 0 s