Kromschröder - BCU 460W3P2C0D0000K1E1-/LM400WF0O0E1-
burner control On-site housing, for controlling, firing and monitoring from pulse-controlled, modulating or stage-controlled gas burners. For Continuous operation with ionization monitoring or UV monitoring with UV probe UVD. Intermittent operation with UV sensor UVS. display of program status, the device parameters and the flame signal. manual operation mode. Diagnosis and adjustment of device parameters above optical interface and BCSoft PC software. EU certified, FM and EAC approved, certified for systems up to SIL 3 (corresponds to PL e). Series: standard version Mains voltage: 230 V~, 50/60 Hz Ignition transformer: 8 kV, 12 mA, ED 100% Flange plate: M32 Valve monitoring system: None High Temperature Operation: None Input function: None